Description

The Ekinex® EK-IE1-SEC-TP secure IP interface realizes a bidirectional data connection between a PC or laptop and a KNX bus system via a LAN network.

Supporting the tunneling protocol, the IP interface allows addressing, parameter setting, visualization, protocolling and diagnosis of KNX bus devices via ETS.

It supports up to 8 simultaneous KNXnet/IP tunneling connections. The device features an integrated KNX bus communication module and is designed for mounting on a 35 mm profile rail. The power supply is supplied directly via the KNX bus without requiring an external auxiliary power supply. As a secure interface, the device prevents unauthorized access to the automation system.

Connections and Installation

  • KNX TP standard red/black bus terminal connection
  • Standard RJ45 Ethernet port for local network (LAN) connection
  • Mounting on 35 mm profile rail according to EN 60715 (1 modular unit = 18 mm)
  • Power supplied directly via KNX bus line (21-30 Vdc) with no external power supply needed

Technical Data

Power Supply21–30 Vdc supplied via KNX bus
Current Consumption20 mA from KNX bus
Simultaneous ConnectionsUp to 8 KNXnet/IP tunneling connections
Network Interface10/100 BaseT Ethernet (RJ45 connector)
Security ProtocolKNX Data Security (AES-128)
Operating Temperature-5 °C ... +45 °C
Relative Humidity5 ... 93 % (non-condensing)
Housing MaterialPolycarbonate (PC) plastic
Protection DegreeIP20 (installed device, EN 60529)
Dimensions1 modular unit (18 x 90 x 60 mm)
WeightApprox. 40 g

Functions / Features

Bidirectional secure data connection between PC and KNX bus system via LAN network
Support for up to 8 simultaneous independent KNXnet/IP tunneling connections
KNX Data Security technology support (AES-128 encryption), configurable via ETS®
Programming push-button and red programming LED on the front panel
LEDs for status and data traffic indication on bus line and Ethernet network
Front-panel push-buttons for special functions and test mode activation
Direct power supply from KNX bus line without requiring auxiliary power unit
Compact 1 modular unit (18 mm) DIN-rail mount plastic housing

Configuration and Commissioning

ETS5 or later is required for configuration and commissioning. A detailed description of the parameters can be found in the application manual of the device. Application programs for ETS: APEKIE1SECTP##.knxprod (## = version).

Documentation and Downloads

Technical Datasheet

STEKIE1IF1SECTP_EN• v. 1.0(29/11/2022)• PDF• 633,1 KB

Instructions Manual

FISPIE1IF1STPIE0• v. 1.0(16/09/2022)• PDF• 652 KB

Application Manual

MAEKIE1IF1SECTP_EN• v. 1.0(07/10/2022)• PDF• 2 MB

Application Software for ETS

APEKIE1SECTP01• v. 1.0(09/09/2022)• KNXPROD• 105,8 KB

CE Conformity Declaration

CEDIEKIE1SECTP• v. 1.0(09/09/2022)• ZIP• 844,4 KB

UKCA Statement

UKCAEKIEIF1SECTP• v. 1.0(14/04/2024)• PDF• 436,4 KB

KNX Certification

KNX_Certification_EK-IE1-SEC-TP• v. 1.0(08/09/2022)• PDF• 774,4 KB

CAD Drawing (DXF)

DQEKIE1TPSEC• DXF• 504 KB